HIGH🇬🇧 English

CVE-2018-16556

CVSS 7.5v3.1pub. 2018-12-13upd. 2024-11-21

A vulnerability has been identified in SIMATIC S7-400 CPU 412-1 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416-2 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416F-2 DP V7 (All versions), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 417-4 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 PN V7 (All versions < V7.0.3), SIMATIC S7-400 H V4.5 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.9), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-410 CPU family (incl. SIPLUS variants) (All versions < V8.2.1), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 V7 (All versions), SIPLUS S7-400 CPU 417-4 V7 (All versions). Specially crafted packets sent to port 102/tcp via Ethernet interface, via PROFIBUS, or via Multi Point Interfaces (MPI) could cause the affected devices to go into defect mode. Manual reboot is required to resume normal operation. Successful exploitation requires an attacker to be able to send specially crafted packets to port 102/tcp via Ethernet interface, via PROFIBUS or Multi Point Interfaces (MPI). No user interaction and no user privileges are required to exploit the security vulnerability. The vulnerability could allow causing a denial of service condition of the core functionality of the CPU, compromising the availability of the system.

oryginał EN
CVSS Vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
  • Siemens Simatic S7 400

    HW
    Siemens
    wszystkie wersje
  • Siemens Simatic S7 400 Firmware

    OS
    Siemens
    ≤ v6.0
  • Siemens Simatic S7 400h

    HW
    Siemens
    wszystkie wersje
  • Siemens Simatic S7 400h Firmware

    OS
    Siemens
    ≤ v4.5
  • Siemens Simatic S7 400h V6

    HW
    Siemens
    wszystkie wersje
  • Siemens Simatic S7 400h V6 Firmware

    OS
    Siemens
    wszystkie wersje
  • Siemens Simatic S7 400 Pn\/dp V7

    HW
    Siemens
    wszystkie wersje
  • Siemens Simatic S7 400 Pn\/dp V7 Firmware

    OS
    Siemens
    wszystkie wersje
  • Siemens Simatic S7 410

    HW
    Siemens
    wszystkie wersje
  • Siemens Simatic S7 410 Firmware

    OS
    Siemens
    < 8.2.1
🔵
ZWERYFIKUJ U PRODUCENTA
Brak jednoznacznych danych o patchu. Sprawdź referencje od producenta.
Tagi
DoS
CWE
Referencje

Powiązane podatności

CVE-2021-40368HIGH7.5ten sam produkt

A vulnerability has been identified in SIMATIC S7-400 CPU 412-1 DP V7 (All versions), SIMATIC S7-400 CPU 412...

CVE-2019-10936HIGH7.5ten sam produkt

Affected devices improperly handle large amounts of specially crafted UDP packets. This could allow an unau...

CVE-2018-16557HIGH8.2ten sam produkt

A vulnerability has been identified in SIMATIC S7-400 CPU 412-1 DP V7 (All versions), SIMATIC S7-400 CPU 412...

CVE-2018-4850HIGH7.5ten sam produkt

A vulnerability has been identified in SIMATIC S7-400 (incl. F) CPU hardware version 4.0 and below (All versio...

CVE-2017-12741HIGH8.7ten sam produkt

Specially crafted packets sent to port 161/udp could cause a denial of service condition. The affected devices...