Omron CS series, CJ series, and CP series PLCs through 2022-05-18 use cleartext passwords. They feature a UM Protection setting that allows users or system integrators to configure a password in order to restrict sensitive engineering operations (such as project/logic uploads and downloads). This password is set using the OMRON FINS command Program Area Protect and unset using the command Program Area Protect Clear, both of which are transmitted in cleartext.
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:NOmron Cp1w Cif41
HWOmronall versionsOmron Cp1w Cif41 Firmware
OSOmronall versionsOmron Cx Programmer
APPOmron< 9.6Omron Sysmac Cj2h
HWOmronall versionsOmron Sysmac Cj2h Firmware
OSOmron< 1.5Omron Sysmac Cj2m
HWOmronall versionsOmron Sysmac Cj2m Firmware
OSOmron< 2.1Omron Sysmac Cp1e
HWOmronall versionsOmron Sysmac Cp1e Firmware
OSOmron< 1.30Omron Sysmac Cp1h
HWOmronall versionsOmron Sysmac Cp1h Firmware
OSOmron< 1.30Omron Sysmac Cp1l
HWOmronall versionsOmron Sysmac Cp1l Firmware
OSOmron< 1.10Omron Sysmac Cs1
HWOmronall versionsOmron Sysmac Cs1 Firmware
OSOmron< 4.1
Related vulnerabilities
Brak uwierzytelnienia kryptograficznego w sterownikach PLC Omron SYSMAC
Omron CX-Programmer i PLC CJ2: przesyłanie hasła w postaci jawnej
Use after free vulnerability exists in CX-Programmer Ver.9.79 and earlier. By having a user open a specially c...
Use after free vulnerability exists in CX-Programmer Ver.9.79 and earlier. By having a user open a specially c...
Use after free vulnerability exists in CX-Programmer Ver.9.79 and earlier. By having a user open a specially c...